Recooling options

 

The technology of recooling has a great influence on the operating costs and the efficiency of the entire absorption chiller. There are several ways to recool absorption chillers.

 

Dry cooler

  • Dry coolers in the summer reach a recooling temperature, which is higher than the outside temperature.
  • The higher the recooling temperature, the higher the required heating temperature.
  • In most cases, operation with a dry cooler is not possible, at least in midsummer.

 

Evaporative cooler / open cooling tower

  • Most reasonable technical solution
  • High annual water consumption
  • Constantly high power requirement for the cooling water pump
  • Water quality management according to VDI 2047

 

Evaporative condenser

  • Slightly more expensive than evaporative coolers
  • High annual water consumption
  • Utilization of the thermosiphon effect for heat transport (ammonia vapour/ condensate)
  • Only a smaller spray water pump is required, but no cooling water pump
  • Water quality management according to VDI 2047

 

Hybrid cooler/ hybrid condenser

  • Very expensive
  • Water demand only approx. 35 % per year (cf. open cooling tower)
  • Spray water pump only in wet operation
  • No cooling water pump required for the condenser version
  • Water quality management according to VDI 2047

 

Adiabatic condenser

  • Usually somewhat cheaper than hybrid condensers
  • Water demand only approx. 10 % per year (cf. open cooling tower)
  • No pump required
  • City water is sufficient
  • No water quality management according to VDI 2047
  • Slightly higher recooling temperatures → slightly lower cooling capacity in summer